How do insurer requirements affect the choice of fire-resistance rating?

Mark Asscheman ·
Industrial fire door with certification label and open insurance policy document on concrete floor, dramatic side lighting

Insurer requirements for fire resistance ratings often exceed the minimum classifications set by building regulations. Where a building code establishes a baseline, an insurer may impose a stricter classification based on the risk profile of the facility, the value of the assets inside it, or the consequences of a fire spreading beyond a single compartment. For architects and facility managers specifying fire-rated doors, this means the regulatory minimum is rarely the only benchmark that matters. The questions below address how insurer requirements work in practice and what they mean for your fire door specification.

How do insurer requirements differ from building code minimums?

Building codes such as the Dutch BBL set the absolute minimum fire-resistance classification a building must meet to receive a permit. Insurer requirements are separate, commercially driven conditions that a property or liability insurer may impose as a condition of coverage. Insurers are not bound by the regulatory floor and will frequently require a heavier classification than the code demands.

The distinction matters because both sets of requirements must be satisfied independently. A fire door that meets the BBL minimum may still leave a facility uninsurable at acceptable premiums if the insurer’s own risk assessment concludes the classification is insufficient. In practice, the insurer’s requirement often becomes the effective design target, particularly in high-value industrial facilities, logistics centres, and buildings containing hazardous materials or sensitive equipment.

It is also worth noting that building codes set minimums for the entire population of buildings in a regulatory category. Insurers assess individual facilities. A warehouse storing ambient goods and a warehouse storing high-value electronics may both meet the same BBL minimum, but an insurer will treat them very differently. The fire-resistance rating required for insurance purposes is therefore a project-specific figure, not a code-derived constant.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

What factors do insurers use to determine fire resistance requirements?

Insurers determine fire-resistance rating requirements based on a risk assessment of the specific facility. The key factors are the type and value of the contents, the consequence of a fire spreading between compartments, the size and configuration of the building, the speed at which a fire could develop, and the proximity of emergency services. No single formula applies universally.

In industrial and commercial buildings, the following factors most commonly drive insurers toward stricter classifications than the regulatory baseline:

  • Asset value and business interruption exposure: High-value stock, production equipment, or IT infrastructure increases the financial consequence of a fire, which in turn raises the insurer’s interest in limiting fire spread between compartments.
  • Hazardous materials: Facilities storing flammable liquids, chemicals, or other substances subject to sector-specific regulations such as PGS15 may face insurer requirements that mirror or exceed those sector rules.
  • Compartment size and layout: Larger compartments mean a fire has more room to develop before being contained. Insurers may require a heavier fire-resistance classification to compensate for compartment sizes that approach or exceed standard limits.
  • Operational continuity requirements: Where a fire in one part of a facility would halt operations across the entire site, an insurer may require additional protection at compartment boundaries to limit the spread of damage.
  • Sprinkler systems and other active measures: Insurers sometimes adjust fire-resistance requirements based on the presence or absence of active fire suppression. A facility with a fully operational sprinkler system may face different door classification requirements than one relying solely on passive protection.

Because these factors interact in facility-specific ways, the insurer’s requirement should always be obtained in writing and reviewed alongside the fire safety engineer’s compartmentalisation design. The two should be reconciled before the door specification is finalised.

What’s the difference between EW and EI classifications for insurer purposes?

For insurer purposes, the core difference between EW and EI classifications is whether the door limits temperature rise on the side not exposed to fire. An EW-classified door maintains integrity and limits radiant heat transfer through the door. An EI-classified door does both of those things and additionally limits the temperature rise on the unexposed face, with EI1 applying the stricter temperature criterion and EI2 permitting a higher temperature rise.

Insurers who specify a fire-resistance classification are typically concerned with whether a fire in one compartment can cause ignition, injury, or damage in an adjacent compartment. The W criterion, which is the Dutch standard baseline classification, limits radiant heat transfer but does not control the temperature rise on the unexposed face. In situations where the insurer’s concern is protecting people, heat-sensitive equipment, or materials that could ignite at elevated temperatures on the far side of the door, an EI1 or EI2 classification may be required rather than EW.

The practical implication for door selection is significant. An EI1 60 door and an EW 60 door both provide 60 minutes of fire resistance, but they differ in what that resistance covers. The EI1 60 door limits temperature rise on the unexposed face to the stricter criterion; the EW 60 door does not. An insurer specifying EI1 60 is not simply asking for a longer duration but for a different type of performance. Substituting an EW door of any duration does not satisfy an EI1 or EI2 requirement, and vice versa.

When reviewing an insurer’s fire-resistance requirement, always confirm whether the specification refers to EW, EI1, or EI2, and for how many minutes. These are not interchangeable, and the distinction has direct consequences for which door products are eligible for the application.

When should the fire door classification be confirmed with the insurer?

The fire door classification should be confirmed with the insurer before the specification is finalised, not after the order is placed. Confirming the insurer’s requirement at the design development stage allows the architect or facility manager to align the fire door specification with both the regulatory minimum and the insurer’s condition in a single coordinated step, avoiding costly substitutions later in the project.

In practice, there are several points in a project lifecycle where the insurer’s requirement becomes critical:

  1. At the design development stage: When the compartmentalisation strategy is being drawn up, the insurer’s classification requirement should be one of the inputs alongside the fire safety engineer’s calculation and the applicable building regulations.
  2. Before committing to a product: Once a door type and classification are under consideration, confirm that the proposed classification satisfies the insurer’s written requirement. Do not assume that meeting the BBL minimum is sufficient.
  3. When the facility use changes: If the building’s function, contents, or occupancy changes after the original specification, the insurer’s requirements may also change. A door that satisfied the insurer’s conditions at handover may not satisfy them after a change of use.
  4. At policy renewal: Insurers periodically reassess risk. A requirement that was acceptable at the time of original installation may be reviewed and tightened at renewal, particularly if the risk profile of the facility or the surrounding area has changed.

Obtaining the insurer’s fire-resistance requirement in writing is essential. Verbal confirmation is not sufficient for a specification file that will be reviewed by a building inspector, a permit authority, or the insurer’s own loss assessor after an incident.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

Can a door certified to European standards satisfy insurer requirements?

Yes, a door CE-certified and tested to European standards can satisfy insurer requirements, provided the classification matches what the insurer has specified. CE certification under EN 16034 and EN 13241, combined with a classification report from an accredited testing body, gives insurers the documented evidence they need to confirm that the door has been independently tested and classified for the stated fire-resistance performance.

European fire-resistance classifications are defined under EN 13501-2 and are produced from fire tests carried out under EN 1634-1. These are internationally recognised standards. An insurer specifying EI1 60 or EW 90 is using the same classification system that European testing laboratories and certification bodies use, which means a CE-certified door with the corresponding Efectis classification report directly addresses the insurer’s stated requirement.

What matters for the insurer’s file is not just the classification itself but the supporting documentation. A CE declaration of performance, a classification report from an accredited laboratory, and the certificate number from a notified body together form a traceable evidence chain. Insurers and their loss assessors can verify these documents independently. A door supplied without this documentation cannot be verified, which creates a gap in the insurer’s risk assessment regardless of what the door label states.

Metacon-Next’s fire-rated industrial doors are CE-certified and tested by Efectis, with classification reports, declarations of performance, and CE certificate numbers available at the specification stage. This means the documentation an insurer requires to confirm compliance can be assembled before commitment to a product, rather than chased after installation.

One important qualification: whether a specific CE-certified classification satisfies a specific insurer’s requirement depends on what the insurer has actually specified. If the insurer requires EI1 60 and the proposed door is classified EW 60, the European certification does not bridge that gap. The classification, not just the certification framework, must match. Always confirm the insurer’s exact requirement and compare it directly against the classification report for the door under consideration.

For facilities where passive fire protection must be both documented and defensible, working with a manufacturer that publishes its technical documentation openly is a practical advantage. Architects and facility managers specifying fire-rated doors for insured facilities can contact Metacon-Next to confirm which classification reports and CE certificates apply to a given product and opening configuration, ensuring the specification file is complete before the insurer reviews it.

If you are at an early stage of a project and need to understand which classifications are available across different door types and opening sizes, the Metacon-Next product range covers classifications from EW 60 through to EI1 120 and EW 240, with full technical documentation available for each. For project-specific guidance on which classification your insurer’s requirement maps to, a quotation request is the appropriate starting point, and a qualified fire safety engineer should be involved in confirming the final specification.

Insurer requirements are one of several layers that shape the fire-resistance rating required for an industrial building. The others include the BBL minimum, sector-specific regulations such as PGS15, the project’s compartmentalisation calculation, and the client’s own risk tolerance. Each layer must be addressed separately and reconciled in the final specification. Learn more about Metacon-Next’s approach to fire-rated door solutions, or explore the company background to understand the manufacturing and certification standards behind each product.