A fire-rated rolling shutter works by remaining open during normal operations and closing automatically when a fire detection system triggers the release mechanism. Once closed, the shutter forms a certified barrier within a fire compartment boundary, containing flames, hot gases, and radiant heat for a defined period, typically between 60 and 240 minutes, depending on the product’s classification under EN 13501-2. The sections below answer the most practical questions architects and facility managers ask when specifying these systems for production environments.
What triggers a fire-rated rolling shutter to close?
A fire-rated rolling shutter closes when a fire detection signal is received by its control system. In most installations, this signal comes from a smoke detector, heat detector, or the building’s central fire alarm panel. On receiving the signal, the shutter’s motor releases and the curtain or door descends under gravity or motor assistance, closing the opening within the compartment boundary.
Most fire-rated rolling shutters also include a manual release mechanism, allowing the shutter to be closed by hand in the event of a power failure or system fault. This is a standard safety requirement, not an optional feature. The closing speed is controlled to prevent impact injuries while still ensuring the shutter reaches the closed position within the timeframe required by the fire safety design.
Some installations integrate the shutter directly with the facility’s building management system, enabling zone-specific responses. In a production hall with multiple compartments, for example, only the shutters within the affected zone may close, keeping unaffected areas operational. This level of integration requires careful coordination between the shutter specification and the facility’s detection and alarm infrastructure during the design phase.
Need advice for your project?
Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.
How does a fire shutter actually contain fire and smoke?
A fire-rated rolling shutter contains fire by forming a physical, tested barrier across an opening that prevents flames, hot gases, and radiant heat from passing through for the duration stated in its classification. The shutter achieves this through the combination of a reinforced curtain or door panel, perimeter sealing, and intumescent materials that expand under heat to close any gaps between the shutter and its guides or floor contact point.
The performance of the shutter is defined by its classification under EN 13501-2, which uses a combination of criteria:
- E (integrity): the shutter prevents flames and hot gases from passing through
- W (radiation reduction): the shutter limits radiant heat transfer through the closed door; this is the Dutch standard baseline criterion
- I1 or I2 (insulation): the shutter limits temperature rise on the unexposed side; EI1 applies the stricter temperature-rise limit, while EI2 permits a higher temperature rise on the unexposed face
A shutter classified EW 60, for example, maintains integrity and limits radiant heat transfer for 60 minutes during a standardised fire test. A shutter classified EI2-120 maintains integrity and limits temperature rise on the unexposed side according to the EI2 criterion for 120 minutes. These are meaningfully different performance levels, and the distinction matters for how the shutter is positioned within a fire compartment strategy.
Smoke containment is a separate performance criterion governed by EN 1634-3, classified under EN 13501-2 as well. Not every fire-rated rolling shutter carries a smoke control classification, and fire resistance and smoke resistance should not be assumed to come together automatically. The specification must confirm both if both are required.
What fire resistance classifications apply to rolling shutters?
Fire-rated rolling shutters are available across a wide range of classifications under EN 13501-2, from EW 60 at the lower end to EI2-120 and EW 240 at the higher end. The appropriate classification for any given opening depends on the project’s fire safety calculation, not on the shutter type alone.
The range of Metacon-Next’s fire-rated industrial doors illustrates the breadth available in practice:
- RGT EW 60 Compact: roller curtain, EW 60, suited to smaller openings up to 48 m²
- RGT EW 60 / EW 90: standard roller curtain, openings up to 48 m²
- RGT EI1 45 / EI2 60 / EW 120: roller curtain with combination classification, bidirectional option available
- RGT EI1 60 / EI2 120 / EW 120: highest listed roller curtain class, openings up to approximately 160–180 m²
- RGS EW 60 / 90 / 120: steel roller door, also available as a TWIN version
- RGS EW 240: steel roller door with four-hour fire resistance, rare in Europe
- RGS EI1 30 / EI2 60: fully insulated roller door
- RGC EI1 60 / EW 60: compact roller door, also available with a liquid-tight seal
The classification a project requires depends on the fire compartmentalisation design, any applicable sector regulation such as PGS15 for chemical storage, client requirements, and insurer requirements. A qualified fire safety engineer should confirm the required classification for the specific building. Whether EW 60 is sufficient or whether EI2-60 or a heavier classification is needed cannot be determined from the door specification alone.
Where in a production facility are fire shutters typically required?
Fire-rated rolling shutters are typically required at openings that cross a fire compartment boundary within a production facility. These boundaries are defined by the facility’s fire compartmentalisation strategy and are intended to limit the spread of fire from one section of the building to another. Common locations include openings between production halls and storage areas, passages between process zones, and connections to loading docks or dispatch areas.
In production environments, the operational requirements of the facility often determine the door type. Forklift passages, goods transport routes, and large equipment access points require openings that a standard hinged fire door cannot practically serve. Rolling shutters and roller curtains are particularly well suited to these situations because they retract into a compact housing above the opening during normal operations, preserving clear height and throughput without obstructing daily workflow.
Specific applications where fire-rated rolling shutters are frequently specified include:
- Openings between production and warehouse zones in logistics and manufacturing facilities
- Access points in chemical or pharmaceutical production areas, where a liquid-tight seal may also be required
- Compartment boundaries in food-processing facilities where liquid handling creates additional containment requirements
- Large openings in data centres and healthcare complexes where compartmentalisation is critical and standard door formats are impractical
The exact locations where a fire shutter is required, and the classification it must achieve, are determined by the building’s fire safety design and compartmentalisation calculation. Sector-specific regulations, such as PGS15 for hazardous substance storage, can impose requirements that exceed the regulatory baseline. A fire safety engineer should be consulted to establish the compartment boundaries and the performance requirements at each opening.
What documentation should a fire shutter come with?
A CE-certified fire-rated rolling shutter should come with a Declaration of Performance, a classification report from an accredited testing laboratory, and a CE certificate. These three documents together provide the traceable evidence that the shutter has been tested, classified, and certified in accordance with European standards, information that is essential for permit applications, insurance documentation, and tender submissions.
For industrial fire-rated shutters, CE marking is governed by two standards simultaneously: EN 16034, which covers the fire- and smoke-resistant closing function, and EN 13241, which applies to industrial doors generally. Both are relevant and should not be treated as interchangeable or alternative requirements.
The classification report is the most technically detailed document in the set. It records the conditions of the fire test, the dimensions tested, and the extended application range within which the classification remains valid. Architects and specifiers should request this report at the specification stage, not after an order has been placed, because it confirms whether the tested dimensions cover the opening being specified. If the opening exceeds the extended application range, the classification cannot be applied without a separately tested or assessed solution.
For projects pursuing BREEAM or LEED certification, or where clients require environmental transparency, Environmental Product Declarations are increasingly relevant. Metacon-Next published EPDs in 2025 for eleven of its main product lines, including the RGT roller curtain range, the RGS roller door range, the RGC compact roller door, and the OHD-C overhead door series. EPDs are standardised environmental documents quantifying lifecycle impact; they are information documents, not sustainability awards, but they allow specifiers to close a documentation file without requesting additional paperwork later.
All Metacon-Next classification reports are issued by Efectis, an internationally accredited fire-safety testing organisation. CE certificates are issued through accredited notified bodies. This documentation is available at the specification stage, which is the point at which it is most useful for architects and engineering consultancies working through a permit or tender process.
Need advice for your project?
Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.
How is a fire-rated rolling shutter different from a standard industrial shutter?
A fire-rated rolling shutter is a certified life-safety system that has been tested and classified for its ability to resist fire for a defined period. A standard industrial shutter is a functional access control product with no fire-resistance classification. The physical appearance may be similar, but the materials, construction, sealing, testing history, and regulatory status are fundamentally different.
The key distinctions in practical terms are:
- Testing and classification: A fire-rated shutter has been tested to EN 1634-1 and classified under EN 13501-2. A standard shutter has not. The classification code, such as EW 60 or EI2-120, is the result of that test, not a manufacturer’s claim.
- CE marking: A fire-rated industrial shutter carries CE marking under both EN 16034 and EN 13241. A standard industrial shutter carries CE marking under EN 13241 only, without the fire-resistant closing function.
- Intumescent sealing: Fire-rated shutters incorporate intumescent materials in their guides, perimeter seals, and bottom bar. These materials expand when exposed to heat, closing gaps that would otherwise allow flames and hot gases to pass through. Standard shutters do not include these components.
- Automatic release mechanism: Fire-rated shutters are required to close automatically on a fire signal. Standard shutters typically operate on demand only.
- Documentation: A fire-rated shutter comes with a classification report, Declaration of Performance, and CE certificate. A standard shutter does not carry this documentation set.
For architects and facility managers, the practical consequence is that a standard industrial shutter cannot be substituted for a fire-rated one at a compartment boundary, regardless of its physical similarity. The compartment boundary requires a tested, certified, and documented system, and only a product that carries the relevant classification report and CE documentation satisfies that requirement.
Metacon-Next’s fire-rated industrial door range is custom-manufactured at its production facility in Moordrecht and developed by an in-house R&D department, meaning that non-standard opening dimensions can be addressed without compromising the classification. All products are tested by Efectis and CE-certified, with full technical documentation available for review before commitment to a product. For specifiers who need to justify their material choice to a building inspector, permit authority, or insurer, that documentation is the foundation of a defensible specification.
If you are working on a project that requires fire-rated rolling shutters and need to confirm which classification applies to your specific openings, contact Metacon-Next directly or request a quotation to discuss your project requirements with their technical team. The required classification should always be confirmed by a qualified fire safety engineer based on the building’s fire safety calculation, but having the right product documentation ready from the outset makes that process considerably more straightforward.
Related Articles
- What does cradle-to-cradle mean for fire-rated doors?
- What are the fire safety requirements for an industrial building?
- What are the consequences of installing the wrong fire class door in a fire?
- What fire safety rules apply when renovating an existing building?
- Can an electric fire door meet EI fire resistance requirements?