How does PGS 15 affect the use of fire-rated doors in storage areas?

Mark Asscheman ·
Fire-rated steel door sealed in a warehouse corridor, with chemical drums on shelving visible through reinforced glazing.

PGS 15 imposes specific fire safety requirements on storage areas for packaged hazardous substances that go beyond the minimum thresholds set by the Dutch BBL. For architects and facility managers specifying fire-rated doors in these environments, the regulation introduces additional obligations around fire compartmentation, door classification, and documentation that must be addressed at the design stage. The sections below work through the most common questions that arise when specifying industrial fire doors for PGS 15 storage areas.

What fire door requirements does PGS 15 actually impose?

PGS 15 imposes fire safety requirements for the storage of packaged hazardous substances that can exceed the baseline requirements of the BBL. The regulation addresses fire compartmentation, ventilation, containment, and the fire resistance of separating constructions, including door openings, to limit the consequences of a fire or spill in a storage area. The specific requirements that apply to a given facility depend on the hazard category of the substances stored, the storage quantity, and the building configuration.

In practice, PGS 15 functions as a sector-specific layer on top of the general building regulations. Where the BBL establishes the absolute minimum, PGS 15 can mandate a heavier fire resistance classification for the compartment boundaries that separate a hazardous storage area from adjacent spaces. This means that a door opening that might satisfy the regulatory baseline in a standard warehouse context may not satisfy the requirements in a PGS 15 storage facility.

The regulation also addresses containment of firefighting water and spilled liquids. This is where the physical characteristics of the door assembly matter beyond its fire resistance classification alone. A door that seals the base of the opening against liquid escape is a relevant technical consideration in these environments, and this requirement must be addressed separately from the fire resistance classification itself.

Because the requirements depend on the specific substances, quantities, and configuration involved, the applicable fire door specification for a PGS 15 facility must be established through a project-specific fire safety design. A qualified fire safety engineer should confirm the required classification and any additional functional requirements before the specification is finalised.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

How does PGS 15 differ from standard building code fire door rules?

The key difference between PGS 15 and standard building code requirements is that PGS 15 is a sector-specific regulation that can require a heavier fire resistance classification and additional functional properties than the BBL baseline. The BBL sets the minimum threshold that applies to all buildings; PGS 15 adds requirements specific to facilities where hazardous substances are stored, based on the nature and scale of the hazard.

Under the BBL, the typical Dutch baseline classification for fire-compartment boundaries is EW60. This means the door maintains integrity and limits radiant heat transfer for 60 minutes. The W criterion is the Dutch standard baseline criterion, and EW60 represents the minimum starting point in many standard building situations. For a standard industrial facility without hazardous substance storage, this baseline may be the only regulatory driver for the door specification.

PGS 15 changes this picture in two ways. First, it can require a higher fire resistance classification than EW60, which may mean specifying a door classified EI1-60, EI2-60, EI1-120, or another classification that includes the insulation criterion. The insulation criterion limits temperature rise on the unexposed face of the door: EI1 applies the stricter limit, EI2 permits a higher temperature rise. Second, PGS 15 introduces requirements that go beyond the fire resistance classification itself, including containment of liquids at the base of the door opening.

It is important not to treat the BBL and PGS 15 as competing standards. They operate at different levels. The BBL is the regulatory floor; PGS 15 is a sector-specific overlay. A facility subject to PGS 15 must satisfy both, and the more demanding requirement governs. The architect or specifier cannot rely on BBL compliance alone to close the specification for a PGS 15 storage area.

Which fire resistance classification is needed under PGS 15?

There is no single fixed fire resistance classification that PGS 15 prescribes for all storage areas. The required classification depends on the specific fire safety design for the facility, including the hazard category of the stored substances, the compartment configuration, and any deviations from the standard regulatory situation. A project-specific fire safety calculation, carried out by a qualified fire safety engineer, is the only reliable basis for determining the required classification.

That said, PGS 15 storage areas frequently require a classification that includes the insulation criterion rather than the W criterion alone. Where the Dutch baseline of EW60 limits radiant heat transfer through the door, an insulation-classified door (EI1 or EI2) limits the temperature rise on the unexposed face. In environments where adjacent areas are occupied or where the risk profile of the stored substances makes temperature control on the safe side important, the insulation criterion is a relevant factor in the fire safety design.

When specifying for PGS 15 applications, it is also worth noting that the duration of fire resistance required may exceed 60 minutes. Classifications of EI1-60, EI2-90, EI1-120, or higher are not unusual in demanding industrial storage environments. The fire safety engineer will determine the required duration based on the compartmentalisation strategy and evacuation requirements for the specific facility.

Architects specifying fire-rated doors for PGS 15 storage areas should not make a classification choice based on the Dutch baseline alone. The project’s fire safety documentation must drive the specification, and the door classification must be confirmed before the order is placed. Requesting the full documentation package from the manufacturer at the specification stage, rather than after commitment, is essential for closing the permit file without delays.

What documentation must a fire door have to satisfy PGS 15 audits?

A fire door installed in a PGS 15 storage area must be supported by a complete set of qualification documents that together prove the door’s fire resistance classification, its conformity with European standards, and the conditions under which the classification was achieved. In a PGS 15 audit context, the absence of any part of this documentation package is a compliance risk that cannot be resolved after installation.

The documentation package for a compliant industrial fire door consists of three core elements:

  • CE certificate: The CE certificate demonstrates that the product conforms to the European Construction Products Regulation. For industrial fire doors, CE marking is required under both EN 16034 (the fire and smoke resisting closing function) and EN 13241 (industrial doors generally). These two standards apply simultaneously and are not interchangeable. The CE certificate is the formal market-access document required for EU installations.
  • Classification report: The classification report is the underlying test report from an accredited fire safety laboratory. It contains the actual fire test results and forms the technical basis for the CE certificate. The classification report specifies the exact conditions under which the fire resistance classification was achieved, including the tested dimensions, installation configuration, and hardware used. This is the document that confirms whether the door’s classification applies to the specified opening dimensions.
  • Declaration of Performance: The Declaration of Performance is the manufacturer’s formal statement of the product’s performance characteristics under the Construction Products Regulation. It links the product to the relevant CE certificate and classification report and is required for any CE-marked construction product placed on the EU market.

For PGS 15 storage areas where a liquid-tight seal at the base of the door is required, the documentation must also cover that functional property. This is a separately tested and certified characteristic, and it must be documented independently of the fire resistance classification. The seal’s performance cannot be inferred from the fire resistance classification alone.

Architects and facility managers should request the full documentation package before committing to a product. A manufacturer that cannot supply classification reports and CE documentation at the specification stage is a risk to the project timeline and the permit process. Metacon-Next provides complete technical documentation, including CE certificates, Efectis classification reports, and Declarations of Performance, for all products in its fire-rated door range.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

Can standard catalogue doors meet PGS 15 storage requirements?

Standard catalogue doors can meet PGS 15 storage requirements, provided the catalogue product’s tested classification matches the classification required by the project’s fire safety design and the door dimensions fall within the tested and certified range for that product. The critical factors are classification adequacy, dimensional compliance with the extended application rules, and the availability of any additional functional properties the facility requires.

The first constraint is classification. A catalogue door with an EW60 classification may not satisfy a PGS 15 storage area that requires an insulation-classified door. The classification must match the project requirement, not simply meet the general Dutch baseline.

The second constraint is dimension. A fire door retains its classification only for openings within the range established by its extended application rules, known as EXAP. If the specified opening exceeds the tested and certified dimensional range for that product, the classification can no longer be applied. In industrial storage environments, openings are frequently sized around operational requirements (forklift passage, goods transport, equipment access) that may exceed standard catalogue dimensions. When an opening falls outside the EXAP range, a separately tested or assessed solution is required.

The third constraint is additional functional properties. If PGS 15 requires a liquid-tight seal at the base of the door opening, that property must be tested and certified for the specific door assembly. It cannot be added to a standard catalogue door without verifying that the combined assembly has been tested in that configuration.

Custom manufacturing addresses the dimension constraint directly. Doors manufactured to order, with classification reports that cover the specified dimensions, allow the architect to close the specification without compromising the fire resistance classification. Metacon-Next manufactures all doors to order at its production facility in Moordrecht, with an in-house R&D department that develops solutions based on market demands and current industry requirements. Architects working on PGS 15 facilities can contact Metacon-Next to confirm which products and classifications are available for the required opening dimensions and functional requirements.

The practical guidance for any PGS 15 project is to start with the fire safety design, establish the required classification and any additional functional requirements, and then identify a certified product that meets those requirements within its documented range. A catalogue door that meets all those criteria is a valid solution. One that does not must be replaced with a product that does, regardless of how well it performs in other respects. For projects where the documentation must be complete before the specification is finalised, working with a manufacturer that publishes its full technical documentation openly is the most efficient way to close the file without chasing paperwork later.

For architects and facility managers specifying fire-rated doors in PGS 15 storage environments, the consistent principle across all of these questions is the same: the fire safety design determines the requirement, and the door specification must match it with documented, certified evidence. If you are working on a PGS 15 project and need to confirm which classifications and documentation are available for a specific application, request a quotation or get in touch with Metacon-Next directly. Learn more about the company and its manufacturing approach on the about us page, or explore the full certified product range at metacon-next.com.