What is a fire-rated overhead door and when should you use one?

Mark Asscheman ·
Fire-rated overhead steel door closed in a warehouse corridor with amber emergency lighting and faint smoke haze at ceiling level.

A fire-rated overhead door is a certified, tested door assembly designed to resist the passage of fire, flames, and hot gases through an opening for a defined period, classified under EN 13501-2 as EW or EI1/EI2 with a time rating in minutes. Unlike a standard overhead door, it forms part of a passive fire protection strategy, functioning as a fire-compartment boundary that can be demonstrated to comply with European testing standards. The sections below address the most common questions architects and specifiers ask when evaluating, classifying, and documenting these systems.

How does a fire-rated overhead door actually work?

A fire-rated overhead door works by forming a tested, certified barrier across an opening that resists the passage of flames, hot gases, and radiant heat for a specified period. The door closes automatically on fire alarm activation and maintains its structural and sealing integrity throughout the rated duration, as verified through standardised fire testing under EN 1634-1.

In normal operation, the door functions like any industrial overhead door, opening and closing to allow goods movement, forklift access, or personnel passage. The fire-resistance function is passive: it activates when needed and requires no manual intervention. The door leaf, frame system, seals, and hardware work together as a tested assembly. Every element contributes to the overall classification, which is why fire-rated industrial door systems are certified as complete assemblies rather than as individual components.

The classification code describes what the door actually resists and for how long. An EW90 overhead door, for example, stops flames and hot gases and limits radiant heat transfer for 90 minutes. An EI1 60 overhead door does the same for 60 minutes while also limiting the temperature rise on the unexposed face to the stricter EI1 threshold. That distinction matters in practice: it affects the door’s construction, weight, and the thermal conditions on the safe side of the compartment boundary.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

What do EI1, EI2, and EW classifications mean for overhead doors?

EI1, EI2, and EW are fire-resistance classifications defined under EN 13501-2. They describe the type of performance a fire-rated overhead door delivers, not just how long it lasts. EW limits radiant heat transfer through the door. EI1 and EI2 both limit temperature rise on the unexposed face, but EI1 applies a stricter threshold than EI2. The number following each code states the duration in minutes.

Breaking down each criterion:

  • E (Integrity): the door prevents flames and hot gases from passing through. All three classifications include E as their foundation.
  • W (Radiation reduction): limits radiant heat transfer through the closed door. W is the Dutch standard baseline criterion and is present in EW-classified doors.
  • I1 (Insulation, stricter criterion): limits the temperature rise on the unexposed side to a lower threshold. EI1-classified doors are constructed to maintain cooler conditions on the protected side.
  • I2 (Insulation, less strict criterion): permits a higher temperature rise on the unexposed side than EI1, while still limiting it. An EI2 90 door and an EI1 60 door are not equivalent: the classification suffix must always be read alongside the duration.

For overhead doors specifically, Metacon-Next’s OHD-C product line covers a range that includes EI1 60, EI2 90, EW 90, and EI1 120 classifications. The OHD-C Sprint high-speed door carries EI2 90 and EW 90 classifications. Which classification is appropriate for a specific project depends on the fire safety calculation for that building, never on the door classification alone. A fire safety engineer should confirm the project-specific requirement.

When is a fire-rated overhead door required instead of a standard one?

A fire-rated overhead door is required wherever an opening crosses a fire-compartment boundary and the fire safety design for that building demands a certified, tested barrier at that location. This is determined by the project’s compartmentalisation calculation, applicable building regulations, and any sector-specific or insurer requirements, not by a universal rule about building type or door size.

In the Netherlands, the BBL (Besluit Bouwwerken Leefomgeving) sets the minimum regulatory baseline, but this baseline is not a single fixed classification that applies to every building. A project may require a heavier classification than the regulatory minimum for several reasons:

  • The building deviates from the standard regulatory situation and a specific fire safety calculation mandates a higher class.
  • Sector-specific regulation applies: for example, PGS15 for chemical storage facilities can impose requirements beyond the general baseline.
  • The client specifies an above-statutory performance level.
  • An insurer requires a stricter classification as a condition of coverage.

In practical terms, fire-rated overhead doors are frequently specified in logistics centres, production halls, pharmaceutical facilities, data centres, and other industrial environments where large openings must remain operationally functional while forming certified compartment boundaries. The decision to use a fire-rated overhead door rather than a standard one is ultimately confirmed by the fire safety engineer and the building permit authority for each project.

What’s the difference between a fire-rated overhead door and a fire-rated sectional door?

A fire-rated overhead door and a fire-rated sectional door are structurally distinct products, though the terms are sometimes used interchangeably in practice. A sectional door opens by lifting the door leaf in horizontal panels along a track system above the opening. An overhead door in the industrial fire-rated context typically refers to a single-piece or multi-section panel that lifts vertically and is stored horizontally overhead; the distinction lies in the panel configuration and track geometry.

From a fire-resistance perspective, what matters most is the tested classification and the EXAP (extended application) range of the specific product, not the general product category name. A fire-rated sectional door and a fire-rated overhead door can carry identical classifications, for example, EI2 90, if both have been tested and classified to that level under EN 1634-1 and EN 13501-2.

The more meaningful comparison for specifiers is between different door types suited to different opening sizes and operational demands. Roller curtains and roller doors are well suited to very large openings because they retract into a compact housing. Overhead and sectional doors offer a rigid panel construction that may be preferred for specific structural or operational requirements. The OHD-C Sprint, for instance, combines fire resistance with high-speed cycle performance, a combination not available in conventional sectional fire doors. Specifying the right type requires matching the opening dimensions, operational frequency, and required fire classification to a product that has actually been tested for that configuration.

What documentation should architects request when specifying a fire-rated overhead door?

When specifying a fire-rated overhead door, architects should request four core documents: the CE declaration of performance, the classification report from an accredited fire testing laboratory, the technical drawings specific to the classified assembly, and, where relevant to the project, an Environmental Product Declaration. These documents together form the technical basis for closing a specification file and defending the material choice to a building inspector or permit authority.

Each document serves a distinct purpose:

  • CE declaration of performance (DoP): the manufacturer’s formal declaration of the product’s performance characteristics under the EU Construction Products Regulation. For industrial fire doors, CE marking is required under both EN 16034 (fire-resisting closing element) and EN 13241 (industrial door, general). These two standards apply simultaneously and are not interchangeable.
  • Classification report: the detailed test outcome from an accredited laboratory, confirming the specific conditions under which the classification was achieved, including tested dimensions, installation configuration, and hardware. For Metacon-Next products, classification reports are issued by Efectis. The OHD-C EI1 60 / EI2 90 / EW 90, for example, is documented under Efectis report 2020-Efectis-R000946.
  • Technical drawings: the drawings must match the classified assembly. A generic drawing cannot be applied across multiple classifications. The drawing must correspond precisely to the classification stated in the specification.
  • EPD (Environmental Product Declaration): increasingly required in BREEAM- and LEED-related projects and European tenders. An EPD quantifies environmental impact across the product lifecycle; it is an information document, not a sustainability award. Metacon-Next published EPDs for 11 product lines in 2025, including the OHD-C EI1 60 (EPD 1.1.00916.2025) and OHD-C EI1 120 (EPD 1.1.00917.2025).

Requesting this documentation at the specification stage (not after the order is placed) is the standard the architect’s workflow should follow. Metacon-Next makes its certificates, classification reports, and EPDs available at specification stage, which allows architects to close a permit file without chasing paperwork later.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

Can a fire-rated overhead door be custom-sized without losing its classification?

Yes, a fire-rated overhead door can be custom-sized without losing its classification, provided the specified dimensions fall within the tested product’s EXAP (extended application) range. EXAP rules, defined under EN 15269, determine how far a fire test result may be extrapolated to door configurations that were not individually tested. As long as the specified opening remains within that range, the classification is retained.

If the required opening exceeds the EXAP range of the tested product, the classification can no longer be applied to that configuration. In that case, the architect must identify a separately tested solution or seek a specific technical assessment. This is not a theoretical risk: industrial openings regularly exceed standard dimensions, and it is one of the most common documentation gaps encountered during specification review.

Custom manufacturing is central to how fire-rated industrial doors are produced for non-standard applications. Metacon-Next manufactures its doors to order at its production facility in Moordrecht, supported by an in-house R&D department, which means non-standard dimensions can be addressed while maintaining classification integrity. The OHD-C EI1 60 / EI2 90 / EW 90, for example, is a standard industrial overhead door with a fire classification that accommodates a range of opening sizes within its documented EXAP limits.

When specifying a custom-dimensioned fire-rated overhead door, the architect should confirm with the manufacturer that the specified dimensions are covered by the classification report before committing to a product. If the opening is at or near the boundary of the EXAP range, that confirmation should be documented in the specification file. For complex or non-standard configurations, contacting Metacon-Next directly at the specification stage is the most reliable way to establish whether a classified solution exists for the required opening.

For projects where fire compartmentation strategy, documentation requirements, or custom dimensions require closer technical review, requesting a quotation early in the design process gives specifiers the product-specific information they need to finalise a defensible specification. More information about Metacon-Next’s manufacturing background and quality certifications is available on the about us page.