What is EN 16034 and why does it apply to fire-rated industrial doors?

Mark Asscheman ·
Industrial fire door with certification markings in a warehouse corridor, lit by amber emergency floor lighting.

EN 16034 is the European harmonised standard that defines the requirements a fire-resisting or smoke-control door must meet to carry CE marking under the Construction Products Regulation. For fire-rated industrial doors, it establishes the testing, classification, and documentation framework that manufacturers must follow before placing a product on the EU market. The sections below unpack the key questions architects and specification writers ask when working with this standard.

What does EN 16034 actually require from a door assembly?

EN 16034 requires that a fire-resisting or smoke-control door assembly be tested and classified according to a defined procedure, and that the manufacturer declare its performance characteristics through a formal Declaration of Performance. The standard covers the fire-resisting and smoke-control closing function of the assembly, meaning the door leaf, frame, hardware, seals, and any hold-open or self-closing devices are all part of what must be assessed.

In practical terms, EN 16034 does not itself specify how the fire test is conducted. The test method is defined in EN 1634-1 for fire resistance and EN 1634-3 for smoke control. EN 16034 references these test methods and establishes which performance characteristics must be declared, including fire resistance duration, smoke leakage, and self-closing behaviour, and how those declarations must be supported by evidence from an accredited notified body.

For an architect or specifier, this means a compliant door assembly must come with a Declaration of Performance that lists each declared characteristic, a classification report from an accredited laboratory confirming the test outcome, and a CE marking that references the standard. An assembly that lacks any of these elements does not meet the EN 16034 framework, regardless of what the manufacturer claims verbally or in a product brochure.

The standard also requires that the assembly as installed reflects the tested configuration. If the tested door used a specific frame profile, a particular intumescent seal, or a defined hardware set, those elements are part of the classification. Substituting components without reassessment risks invalidating the classification, a point that matters significantly when the door is inspected during a permit process or an insurance review.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

How does EN 16034 relate to CE marking for fire doors?

EN 16034 is the harmonised standard under the EU Construction Products Regulation that triggers the obligation to CE mark fire-resisting and smoke-control door assemblies. Once EN 16034 is listed in the Official Journal of the EU as a harmonised standard for a product type, manufacturers placing that product on the EU market must follow its requirements and affix CE marking. Without it, the product cannot legally be placed on the EU market.

CE marking for fire doors is not a quality award or a voluntary endorsement. It is the manufacturer’s formal declaration that the product meets the essential characteristics declared in its Declaration of Performance, assessed and verified through the conformity assessment system specified in EN 16034. For industrial fire doors, this involves a notified body, an accredited third-party organisation, that audits the manufacturer’s factory production control and, where required, performs or oversees product testing.

The notified body’s identification number appears in the certificate number. For example, the number 1812 in a certificate reference such as 1812-CPR-1736 identifies the notified body responsible for that assessment. This traceability is deliberate: it allows any party reviewing the documentation, a building inspector, an insurer, a fire safety engineer, to verify the chain of evidence behind the CE marking.

Metacon-Next’s fire-rated industrial door range carries CE marking across all main product lines, with each certificate referencing the relevant notified body. The CE certificates are available as part of the product documentation package, which also includes the classification report and Declaration of Performance.

What is the difference between EN 16034 and EN 13501-2?

EN 16034 and EN 13501-2 serve different functions within the same compliance framework. EN 16034 is the harmonised product standard that governs CE marking for fire-resisting door assemblies; it defines what must be tested, declared, and documented. EN 13501-2 is the classification standard that translates fire test results into the performance codes used in specifications: EW60, EI1 60, EI2 120, and so on.

In other words, EN 16034 tells manufacturers what they must do to CE mark a fire door. EN 13501-2 tells everyone, manufacturers, architects, engineers, and authorities, how to read and communicate what the door has actually achieved in the fire test.

The two standards work together. A fire door assembly is tested according to EN 1634-1, the test results are classified using EN 13501-2 to produce a classification such as EW 90 or EI1 60, and that classification is then declared on the Declaration of Performance in accordance with EN 16034. The classification report issued by the testing laboratory, in Metacon-Next’s case, Efectis, is the document that connects the test to the classification.

For specifiers, the practical consequence is that both references matter. EN 16034 tells you the door has been through the correct conformity assessment route. EN 13501-2 tells you what the door actually does in a fire. A specification that references only one without the other is incomplete. The classification under EN 13501-2 is what goes into the fire strategy and the permit file; EN 16034 compliance is what makes the CE marking on the product legitimate.

It is also important not to confuse EN 13501-2 with EN 13501-1. EN 13501-1 classifies how materials react to fire: their combustibility, smoke development, and burning droplet behaviour. EN 13501-2 classifies fire resistance: how long a closed assembly maintains its performance under a standardised fire test. For fire-rated industrial doors, EN 13501-2 is the relevant standard.

Which fire resistance classifications fall under EN 16034?

Under EN 16034, fire resistance classifications are expressed using the criteria defined in EN 13501-2: E for integrity, W for radiation reduction, and I for insulation, each combined with a duration in minutes. Common classifications for industrial fire doors include EW 60, EW 90, EW 120, EW 240, EI1 60, EI2 60, EI1 90, EI2 90, EI1 120, and EI2 120. The specific classification a door carries depends on what it achieved in the accredited fire test.

Each criterion means something distinct. E means the door stops flames and hot gases from passing through for the stated period. W means the door limits radiant heat transfer. W is the Dutch standard baseline criterion, relevant when working within Dutch regulatory frameworks. I means the door also limits temperature rise on the unexposed face, with two distinct levels: EI1 applies the stricter temperature limit, while EI2 permits a higher temperature rise on the unexposed side.

It is essential to always specify EI1 or EI2 explicitly. A door classified EI1 60 and a door classified EI2 60 both provide 60 minutes of fire resistance, but they differ on the insulation criterion. That difference can affect door leaf thickness, frame profile, and perimeter sealing, all of which matter when coordinating a specification with the building’s fire strategy.

The duration values in common use are 30, 60, 90, 120, and 240 minutes. A classification of EW 240, for example, means the door maintains integrity and limits radiant heat transfer for four hours, a level of fire resistance that is rare in Europe and is available in specific Metacon-Next product lines such as the RGS EW 240 roller door and the LD Pro pedestrian door.

Whether a particular classification is sufficient for a given project depends on the project’s fire safety calculation, applicable sector regulations, client requirements, and insurer requirements, not on the classification alone. A qualified fire safety engineer should confirm the required classification for each specific building and compartmentalisation design.

What documentation should accompany an EN 16034-compliant fire door?

An EN 16034-compliant fire door must be accompanied by a Declaration of Performance, a CE certificate referencing the notified body, and a classification report from an accredited fire-testing laboratory. These three documents together form the evidence base that an architect, building inspector, or insurer needs to verify that the door meets its stated classification. Requesting this documentation at the specification stage, not after the order is placed, is the correct approach.

The Declaration of Performance is the manufacturer’s formal statement of the product’s declared performance characteristics. It references the harmonised standard (EN 16034), the notified body, and the specific classification achieved. The CE certificate confirms that the factory production control has been assessed and that the product is manufactured consistently with the tested configuration.

The classification report is the most technically detailed of the three. Issued by the testing laboratory, it records the exact conditions under which the classification was achieved: the opening dimensions tested, the frame configuration, the hardware used, the sealing system, and the extended application rules (EXAP) that define how far the classification can be applied to dimensions beyond those directly tested. For architects working with non-standard opening sizes, the EXAP limits in the classification report are critical; if the specified opening exceeds the EXAP range, the classification cannot be applied without a separately tested or assessed solution.

In addition to these three core documents, architects working on projects with sustainability requirements may also need Environmental Product Declarations. EPDs are not a requirement under EN 16034, but they are increasingly requested in BREEAM and LEED projects and in European public tenders. Metacon-Next published EPDs for eleven of its main product lines in 2025, covering products including the RGC EI1 60, the OHD-C EI1 60, and the OHD-C EI1 120, among others.

Manufacturers who cannot supply the classification report and CE documentation before commitment to a product leave a gap in the specification file that will need to be resolved later, often at the worst possible moment in the project timeline. Metacon-Next makes its product documentation available at the specification stage, which allows the permit file to be closed with the correct evidence in place from the outset.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

Does EN 16034 apply to all industrial door types?

EN 16034 applies specifically to fire-resisting and smoke-control door assemblies; it covers the fire and smoke performance function of the door. It does not apply to industrial doors that carry no fire or smoke resistance classification. For industrial doors in general, a separate standard applies: EN 13241, which covers industrial, commercial, and garage doors regardless of whether they have a fire classification.

This distinction matters because an industrial fire door is typically subject to both standards simultaneously, not one or the other. EN 13241 governs the door as an industrial product, addressing characteristics such as mechanical strength, wind load resistance, thermal transmittance, and safe use. EN 16034 governs the fire-resisting function of the same assembly. Both sets of requirements must be met, and both are reflected in the CE marking and Declaration of Performance for a fire-rated industrial door.

Never treat EN 16034 and EN 13241 as alternatives. They address different aspects of the same product and apply in parallel. A roller shutter, overhead door, sliding door, or high-speed door that carries a fire resistance classification must comply with both standards to be correctly CE marked for the EU market.

Within the category of fire-rated industrial doors, EN 16034 applies across door types: roller curtains, steel roller doors, overhead sectional doors, sliding doors, and pedestrian doors can all fall within its scope, provided they are designed and tested as fire-resisting assemblies. The Metacon-Next product range includes all of these types, each tested and classified under the EN 16034 framework with Efectis classification reports and CE certificates to confirm compliance.

For high-speed doors with a fire resistance classification, a relatively rare product type, the same framework applies. The OHD-C Sprint, for example, is classified EI2 90 and EW 90 and carries CE certificate 1812-CPR-1787, making it the only fire-resistant high-speed door in the Metacon-Next range and one of the few such products available in the European market.

If you are working on a project that requires a fire-rated industrial door and need to verify which classifications and documentation apply to a specific opening type or dimension, contact Metacon-Next directly or request a quotation with your technical requirements. A qualified fire safety engineer should confirm the classification required for your specific building and compartmentalisation design before the specification is finalised.