What is the difference between a test report, classification report and EXAP report for fire doors?

Mark Asscheman ·
Steel fire door in an industrial workshop with three certification documents fanned out at its base in a flat vector illustration style.

A fire door’s documentation trail consists of three distinct but related reports: the test report, the classification report, and the EXAP report. The test report records what happened during the fire test itself. The classification report translates those results into a standardised EN 13501-2 code such as EW60 or EI1 60. The EXAP report then defines how far that classification can be extended to door sizes and configurations that were not individually tested. Understanding how these three documents relate to each other is essential for any architect or specification writer closing a permit file or justifying a product choice.

What does a fire door test report actually contain?

A fire door test report is the raw record of a standardised fire resistance test conducted in an accredited laboratory. It documents the conditions of the test, the behaviour of the door assembly throughout, and the measured performance data at each stage. The test follows EN 1634-1, the European standard that defines the fire resistance test method for doors and shutters.

Inside a test report, you will typically find the exact configuration that was tested: the door dimensions, the frame type, the hardware used, the sealing details, and the installation conditions. The report records how the door performed against each criterion over time. For fire resistance under EN 13501-2, the relevant criteria are E (integrity, meaning flames and hot gases are prevented from passing through), W (radiation reduction, which limits radiant heat transfer through the door and is the Dutch standard baseline criterion), and I (insulation, which limits temperature rise on the unexposed face, always specified as either I1 or I2 since they represent different temperature-rise thresholds).

The test report also records the time at which each criterion was met or failed, forming the basis for the classification that follows. It is the primary evidence document and the foundation on which everything else rests. Without a valid test report from an accredited laboratory, no classification can be issued and no CE certificate can be granted.

For Metacon-Next products, fire resistance testing is carried out by Efectis, an internationally accredited fire safety testing institute. Each product line has its own Efectis report number, which can be requested at the specification stage alongside the CE certificate and declaration of performance.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

What is a classification report and how does it differ from a test report?

A classification report is the document that translates fire test results into a standardised performance code under EN 13501-2. Where the test report records the raw data of what happened during the fire test, the classification report interprets those results and assigns the formal classification, for example EW60, EI1 60, or EI2 120. The classification report is the document that architects and authorities refer to when specifying or approving a fire-rated door assembly.

The distinction matters because a test report alone does not tell a specifier which classification the door has achieved. A door might have been tested for 90 minutes but only achieved integrity and radiation reduction, not insulation. The classification report makes that outcome explicit in standardised notation, clearly stating which criteria were met and for how long.

For industrial fire doors, the classification follows EN 13501-2 and combines the relevant criteria with a time value. An EI1 60 classification means the door maintained integrity and limited temperature rise on the unexposed face according to the stricter I1 criterion for 60 minutes. An EI2 90 classification uses the same integrity criterion but applies the less strict I2 insulation threshold for 90 minutes. These are not interchangeable, and a classification report makes the distinction explicit.

In practice, Efectis issues a combined document that contains both the test results and the resulting classification. When Metacon-Next refers to a classification report, this is what is meant: an Efectis-issued document that records the test conditions and formally assigns the EN 13501-2 classification. This document is the technical basis for the CE certificate and the declaration of performance. Architects specifying fire-rated industrial doors from Metacon-Next’s product range can request the relevant Efectis report number for each product line at the specification stage, before committing to a product.

What is an EXAP report and when is it needed?

An EXAP report, short for Extended Application report, defines the range of door sizes and configurations to which a tested classification can be legally applied without conducting an additional fire test. It is needed whenever a specified door opening differs from the exact dimensions and configuration tested in the original fire test, which in industrial practice is almost always the case.

Fire resistance testing is conducted on a specific door assembly at specific dimensions. That test result, on its own, applies only to that exact configuration. Industrial buildings routinely require openings that are wider, taller, or differently proportioned than the tested specimen. The extended application rules, set out in the EN 15269 series of standards, define how test results may be extrapolated to similar but untested configurations while maintaining the validity of the classification.

The EXAP report documents the limits of that extrapolation. It states the maximum and minimum dimensions within which the classification remains valid, any constraints on hardware or frame configuration, and any conditions that must be met for the extended application to apply. If a specified opening falls within the EXAP range, the door retains its full classification for that opening without requiring a new test. If the opening falls outside the EXAP range, the classification cannot be applied, and a separately tested or assessed solution must be found.

For architects working on industrial projects, the EXAP report is often the most practically important of the three documents. Large openings for forklift access, goods transport, or equipment movement frequently push against or beyond standard tested dimensions. Knowing the EXAP limits of a product before specifying it prevents late-stage redesign or substitution. Contact Metacon-Next directly to confirm the EXAP limits for a specific product and opening size at the specification stage.

How far can EXAP extend a fire door classification?

EXAP can extend a fire door classification to a range of sizes and configurations beyond the tested specimen, but the limits are product-specific and defined by the EN 15269 extended application rules. There is no universal answer to how far EXAP reaches. The permissible extension depends on the door type, the construction, the classification achieved in the test, and the rules applicable to that product category.

In general terms, extended application rules allow a tested classification to be applied to doors that are larger or smaller than the tested specimen, provided the structural and performance behaviour can be reliably predicted from the test data. The EN 15269 series sets out the methodology for making that prediction. The resulting EXAP report documents the specific limits: for example, the maximum leaf area, the maximum width and height independently, and any constraints on configuration such as whether a double-leaf version is covered.

For industrial fire doors, this is particularly relevant because operational openings are often large. A roller curtain tested at a given dimension may have an EXAP range that covers openings up to substantially larger areas. The RGT EI1 60 / EI2 120 / EW 120 roller curtain, for instance, covers openings up to approximately 160 to 180 square metres under its extended application. Other products have narrower ranges. The RGT EW 60 Compact is designed for smaller openings up to 48 square metres.

The critical point for specification work is that EXAP limits are fixed boundaries, not guidelines. If an opening exceeds the EXAP range of the selected product, the classification does not apply to that opening. The architect must either select a different product whose EXAP range covers the required dimension, or seek a solution that has been separately tested or assessed for that size. Assuming that a classification extends indefinitely is a documentation risk that can surface during a permit review or building inspection. Requesting the EXAP report at the specification stage, alongside the classification report, closes that gap before it becomes a problem. You can explore the full product documentation available through Metacon-Next’s industrial door range to compare EXAP coverage across product lines.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

Which documents should architects request at the specification stage?

Architects specifying fire-rated industrial doors should request four documents at the specification stage: the classification report, the CE certificate, the declaration of performance, and the EXAP report. These four documents together provide the complete technical basis for a specification that can be defended to a building inspector, permit authority, or client.

  • Classification report: The Efectis-issued document that records the fire test results and assigns the EN 13501-2 classification. It confirms which criteria were tested, under what conditions, and for how long. This is the primary technical evidence for the classification stated in the specification.
  • CE certificate: Issued by an accredited notified body, the CE certificate confirms that the product meets the requirements of the Construction Products Regulation for placing on the EU market. For industrial fire doors, CE marking is mandatory and applies under both EN 16034 (for the fire-resistant closing function) and EN 13241 (for industrial doors generally). These two standards apply simultaneously and are not interchangeable.
  • Declaration of performance (DoP): The manufacturer’s formal declaration of the product’s performance characteristics, required under the CPR. It links the product to its CE certificate and classification report and is the document that formally carries the manufacturer’s responsibility for the stated performance.
  • EXAP report: The extended application document that defines the range of dimensions and configurations to which the classification can be applied. Essential for confirming that the specified opening falls within the scope of the tested classification.

For projects where environmental documentation is required, for example, in BREEAM or LEED assessments or in tenders that request lifecycle impact data, an Environmental Product Declaration should also be requested. Metacon-Next published EPDs for eleven main product lines in 2025, covering products including the RGC EI1 60, OHD-C EI1 60, OHD-C EI1 120, and the LD Pro EI1 60 / EI2 120 / EW 240 pedestrian door, among others. An EPD is a standardised information document quantifying environmental impact across the product lifecycle. It is not an environmental label or sustainability award, but it provides the factual basis that sustainability assessors and clients increasingly require.

The most important practical point is timing. All of these documents should be requested before commitment to a product, not after the order is placed. If a manufacturer cannot supply the classification report, CE certificate, and EXAP report at the specification stage, that is relevant information. Metacon-Next makes its certification documentation available at the specification stage, including classification reports, CE certificates, declarations of performance, and EPDs, so that architects can close a specification file with the evidence already in hand rather than chasing paperwork later in the project lifecycle.

Finally, no documentation package replaces a project-specific fire safety calculation. The classification report confirms what the door has been tested to achieve. Whether that classification is sufficient for a particular fire compartment boundary depends on the compartmentalisation design, applicable sector regulations, client requirements, and insurer requirements for that specific project. For questions about regulatory adequacy, the appropriate reference point is a qualified fire safety engineer or the competent local authority. For questions about product documentation and what is available for a specific Metacon-Next product, request a quotation or get in touch with the team directly.