What should contractors look for when specifying fire-rated industrial doors in 2026?

Mark Asscheman ·
Contractor in hard hat reviewing specifications beside a large industrial fire-rated steel door on a construction site.

When specifying fire-rated industrial doors in 2026, contractors should request the CE certificate, the Efectis classification report, and the Declaration of Performance before committing to any product. These three documents confirm that the door has been independently tested, that its fire-resistance classification is traceable to an accredited fire test, and that the manufacturer is formally accountable for the stated performance. For projects with sustainability requirements, Environmental Product Declarations are increasingly relevant as well. The sections below address the most common technical questions contractors face during the specification process.

What documentation should contractors request before specifying a fire-rated industrial door?

Before specifying a fire-rated industrial door, contractors should request three core documents: the CE certificate, the Efectis classification report, and the Declaration of Performance. These documents together confirm the door’s tested fire-resistance classification, the conditions under which that classification was achieved, and the manufacturer’s formal declaration of performance under the EU Construction Products Regulation. Requesting them at the specification stage, not after order placement, is essential for closing a permit file without delays.

The CE certificate confirms that the product meets European standards and is a prerequisite for placing the door on the EU market. For industrial fire doors, two CE-relevant standards apply simultaneously: EN 16034, which governs the fire- and smoke-resistant closing function, and EN 13241, which applies to industrial doors generally. These are not interchangeable; they address different aspects of the product, and both are relevant to a compliant industrial fire door.

The classification report is the underlying test document from an accredited fire-safety laboratory. It specifies exactly which opening dimensions were tested, what installation conditions applied, and how far the extended application rules (EXAP) allow the classification to be extrapolated to untested configurations. Without this document, a contractor cannot verify whether the classification applies to the actual opening dimensions on the project.

For projects involving BREEAM or LEED assessment, or where clients require sustainability reporting, an Environmental Product Declaration quantifies the product’s environmental impact across its full lifecycle. Metacon-Next published EPDs for eleven of its main product lines in 2025, available at the specification stage so contractors are not chasing paperwork after the order is placed.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

What is the difference between EI1 and EI2 fire door classifications?

EI1 and EI2 both describe insulating fire doors that limit temperature rise on the unexposed side, but they apply different strictness levels to that insulation criterion. EI1 is the stricter criterion, permitting a lower maximum temperature rise on the unexposed face. EI2 permits a higher temperature rise on the unexposed side. A door classified EI1-60 and one classified EI2-60 both provide 60 minutes of fire resistance, but they differ in how much heat is allowed to pass through to the protected side.

This distinction has practical consequences. An EI1-classified door typically requires a thicker leaf, a different frame profile, or additional perimeter sealing to meet the stricter insulation limit. When specifying fire-rated industrial doors, contractors must never use “EI” as a generic label without specifying whether the classification is EI1 or EI2; the two represent meaningfully different performance levels under EN 13501-2, the fire-resistance classification standard.

The choice between EI1 and EI2 is not a matter of preference. It is determined by the project’s fire safety design and compartmentalisation calculation. Whether a specific project requires EI1 or EI2 depends on factors including the building type, applicable sector regulations, client requirements, and insurer requirements, not on a general rule that one classification is universally superior. A qualified fire safety engineer should confirm the required classification for the specific project.

Metacon-Next’s product range covers both criteria across multiple door types. For example, the OHD-C overhead door is available in EI1-60, EI2-90, and EW90 classifications, and the LD Pro pedestrian door is available in EI1-60, EI2-120, and EW240. Reviewing the full product range alongside the relevant Efectis classification reports is the correct starting point for matching the product to the project requirement.

How do EXAP limits affect custom-sized fire door openings?

Extended application rules, known as EXAP and governed by EN 15269, define the range of opening dimensions to which a tested fire-resistance classification can be legitimately applied without conducting a new fire test. If a specified opening falls within the EXAP range of a tested door configuration, the classification holds. If the opening exceeds those limits, the classification can no longer be applied, and the contractor must seek a separately tested or assessed solution.

In industrial environments, this is a frequent challenge. Openings sized for forklift passage, wide goods transport, or equipment access regularly exceed the dimensions covered by standard door catalogues. A door that is CE-certified and Efectis-tested for a given classification retains that classification only within the boundaries defined in its classification report. Specifying a door for an opening that exceeds its EXAP range, and then applying the same classification, is not compliant, regardless of how similar the opening dimensions appear.

The classification report is the document that defines the EXAP limits for each product. This is one of the primary reasons contractors should request the classification report at the specification stage, not after the order is placed. If the manufacturer cannot supply this document before commitment to a product, that gap in documentation should be treated as a material risk.

Custom manufacturing addresses EXAP limits directly when the door itself is manufactured to the required dimensions and tested or assessed accordingly. Metacon-Next produces doors to order at its facility in Moordrecht, supported by an in-house R&D department, which means non-standard openings can be addressed without losing classification integrity. For any opening where standard dimensions are insufficient, contacting Metacon-Next directly to confirm the applicable EXAP range and available solutions is the appropriate next step.

Which fire resistance criteria apply to industrial door openings — EW or EI?

Whether an industrial door opening requires an EW or an EI classification depends on the project’s specific fire safety design and compartmentalisation calculation, not on a general rule tied to building type. Under EN 13501-2, EW means the door provides integrity and limits radiant heat transfer. W is the Dutch standard baseline criterion. EI1 and EI2 add an insulation requirement on top of integrity, limiting the temperature rise on the unexposed side to different degrees of strictness.

The Dutch baseline is EW60, meaning the minimum typically encountered in standard regulatory situations. However, this does not mean EW60 is universally sufficient for every industrial application. A heavier classification may be required when the project deviates from standard building regulations, when sector-specific rules such as PGS15 for hazardous substance storage impose additional requirements, when a client specifies an above-statutory standard, or when an insurer sets stricter conditions.

The BBL (Besluit Bouwwerken Leefomgeving) establishes minimum requirements, but it does not prescribe a single fixed classification for every building type or application. Implying that a particular year’s BBL requirements mandate a specific door classification misrepresents how the regulatory framework operates. The applicable classification for a given opening is determined by the project’s fire safety calculation, carried out by a qualified fire safety engineer.

Contractors specifying fire-rated industrial doors should work from the fire safety engineer’s output, then match the required classification to a product with the appropriate CE certificate and Efectis classification report. Metacon-Next’s range covers EW60 through EW240 and EI1/EI2 classifications across multiple door types, giving specifiers the flexibility to match the product to the verified project requirement rather than defaulting to an assumption.

What should contractors check when a fire door opening exceeds standard catalogue dimensions?

When a fire door opening exceeds standard catalogue dimensions, contractors should first obtain the classification report for the proposed product and verify the EXAP limits it defines. If the opening falls outside those limits, the stated classification cannot be applied to that configuration. The contractor must then either identify a product with a wider tested range, request a project-specific extended application assessment, or confirm that the manufacturer can produce a custom door that has been tested or assessed for the required dimensions.

Three checks are essential in this situation:

  1. Confirm the EXAP range from the classification report. The report specifies the maximum and minimum dimensions for which the tested classification is valid. This is not the same as the maximum physical size the door can be manufactured to; it is the maximum size for which the fire-resistance classification is technically defensible.
  2. Verify that the CE certificate covers the required classification at the required dimensions. CE certification is tied to the tested and assessed configuration. A certificate that covers EI1-60 for openings up to a certain area does not automatically extend to larger openings.
  3. Confirm the documentation trail for the custom configuration. A custom-dimensioned fire door must be supported by documentation that traces its classification to an accredited test or extended application assessment. A drawing or product sheet alone is not sufficient.

Industrial openings frequently require dimensions that go beyond what standard fire door catalogues cover. Metacon-Next’s custom manufacturing capability, backed by its in-house R&D department, is designed precisely for this situation. Contractors can request a quotation for non-standard configurations and confirm the available classifications and supporting documentation before committing to a specification.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

How does ISO 9001 certification affect a fire door manufacturer’s reliability as a supply chain partner?

ISO 9001 certification means the manufacturer operates a structured quality management system that has been independently audited and verified. For contractors evaluating a fire door manufacturer as a supply chain partner, ISO 9001 certification indicates that quality assurance is embedded in the organisation’s processes, from design and production through to documentation and delivery, rather than applied inconsistently. It does not certify the fire performance of individual doors, but it does provide assurance that the systems governing how those doors are produced and documented are subject to ongoing external scrutiny.

In practice, this matters for several reasons relevant to passive fire protection projects:

  • Consistent documentation. A manufacturer with a certified quality management system is more likely to produce complete, accurate, and traceable technical documentation for every product, including classification reports, declarations of performance, and CE certificates.
  • Traceability. ISO 9001 requires that production processes are documented and that deviations are recorded and addressed. For a life-safety product like a fire-rated door, traceability through the production process is a meaningful assurance.
  • Audit readiness. Projects requiring demonstrable due diligence, whether for a building permit, an insurer, or a client audit, benefit from working with manufacturers whose quality systems are independently verified.

Metacon-Next holds ISO 9001 certification for its quality management system, renewed in April 2025, as well as ISO 14001 for its environmental management system. These are company-level certifications that apply to the entire organisation and production process. They complement, but do not replace, the product-level evidence provided by CE certificates and Efectis classification reports.

For contractors building a supply chain for fire-rated industrial doors, combining product-level certification with company-level ISO certification is the strongest basis for demonstrating due diligence. More information about Metacon-Next’s quality credentials is available on the about us page, and the full product documentation portfolio can be reviewed by contacting the team directly.

Related Articles