Which smoke-control classification may be required in addition to a door’s fire-resistance rating?

Mark Asscheman ·
Heavy industrial fire door slightly ajar in a concrete wall, wisps of smoke curling along its sealed edge with dramatic backlit shadows.

A smoke-control classification may be required in addition to a fire door’s fire-resistance rating when the project’s passive fire protection strategy demands that the door also limit smoke leakage, either at ambient temperature, at elevated temperature, or both. Fire resistance and smoke control are separate performance criteria under EN 13501-2, and a door classified EW60 or EI1 60 does not automatically carry a smoke-control classification. Whether a smoke classification is needed depends on the building’s fire safety design, the applicable regulations, and any sector-specific or insurer requirements that go beyond the regulatory minimum. The sections below address the most common questions architects and specifiers ask when working through this distinction.

What are the smoke-control classifications defined in EN 13501-2?

EN 13501-2 defines two smoke-control classifications for doors: Sa and Sm. Sa describes performance at ambient temperature: the door limits smoke leakage when there is no significant temperature difference across it. Sm describes performance at elevated temperature: the door limits smoke leakage under the thermal conditions present during a fire. Both classifications are based on measured leakage rates from testing under EN 1634-3.

These two classifications are independent of each other and independent of the fire-resistance classification. A door may carry Sa alone, Sm alone, both, or neither. The classification is expressed by appending the smoke code to the fire-resistance classification. For example, a door classified EI2 60 Sa carries 60 minutes of fire resistance under the EI2 insulation criterion and also limits smoke leakage at ambient temperature. A door classified EW 90 Sa Sm limits radiant heat transfer for 90 minutes and controls smoke at both ambient and elevated temperatures.

It is worth noting that Sa and Sm are not hierarchical: Sm does not automatically include Sa. Each must be tested and classified separately, and each must appear explicitly in the product’s classification report and declaration of performance if it is to be relied upon in a specification.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

Does every fire door need a smoke-control classification?

No. A smoke-control classification is not automatically required for every fire door. Fire resistance and smoke control are separate performance criteria, and a fire door can be fully compliant with applicable fire-resistance requirements without carrying any smoke classification at all. Whether a smoke classification is needed depends on what the building’s fire safety design requires for that specific opening.

The fire-resistance classifications (E, W, EI1, EI2, combined with a time rating) address the door’s ability to stop flames, limit radiant heat transfer, or limit temperature rise on the unexposed face. None of these criteria directly address smoke leakage. Smoke, particularly in the early stages of a fire when temperatures are still relatively low, can travel through gaps and seals that would otherwise hold under fire-resistance testing conditions.

Where a compartment boundary is required to control smoke movement (for example, to protect an escape route, a stairwell, or a refuge area), the door at that boundary may need to demonstrate smoke-control performance in addition to fire resistance. Whether this applies to a specific opening is a matter for the building’s fire safety calculation and the applicable regulations. A qualified fire safety engineer or the competent authority is the correct reference point for determining whether a smoke classification is required for a given project.

What’s the difference between Sa and Sm on a fire door?

The key difference between Sa and Sm is the temperature condition under which smoke leakage is measured. Sa is tested at ambient temperature (roughly 20°C), representing the early phase of a fire or a scenario where the door is remote from the fire source. Sm is tested at elevated temperature, representing conditions closer to an active fire where the door and its seals are exposed to significant heat.

This distinction matters in practice because a door that controls smoke effectively at ambient temperature may not perform equally well when its seals and frame are thermally stressed. Intumescent seals, for example, expand under heat and can improve smoke control at elevated temperatures, but the tested and classified performance is what counts, not an assumption about how the door will behave.

For architects specifying doors along escape routes or in compartments where early-stage smoke control is the primary concern, Sa is often the relevant criterion. Where the door must control smoke under conditions that accompany active fire (such as a door between a fire compartment and a protected corridor), Sm may be the more demanding and relevant classification. In some specifications, both Sa and Sm are required simultaneously, which means the door must have been tested and classified for each condition independently.

Never assume that a door carrying a fire-resistance classification also carries Sa or Sm. These must appear explicitly in the classification report and the declaration of performance.

How is smoke leakage performance tested and measured?

Smoke leakage performance for doors is tested under EN 1634-3, the dedicated smoke control test method for door assemblies. The test measures the volume of air (used as a proxy for smoke) that passes through the closed door assembly per unit of time, at a defined pressure differential across the door. The result is expressed as a leakage rate in cubic metres per hour per metre of door perimeter or per square metre of door area.

For the Sa classification, the test is conducted at ambient temperature. For the Sm classification, the test is conducted at elevated temperature: the door assembly is pre-conditioned with heat before leakage is measured. The pressure differential used in testing reflects the conditions that a door might experience in a real building, where pressurisation systems or stack effects create a difference in air pressure across a compartment boundary.

Extended application rules under EN 15269 determine how far a tested result can be applied to door configurations that were not individually tested (for example, different sizes or hardware combinations). Just as with fire-resistance classifications, the classification report specifies the tested configuration and the limits within which the classification remains valid. Architects should request the classification report, not just the CE declaration, to confirm that the tested configuration matches the specified opening.

Metacon-Next products are tested by Efectis, an internationally accredited fire-safety testing organisation, and the full range of certified fire-rated industrial doors is supported by classification reports that detail the tested conditions. These reports are available at the specification stage, not only after an order is placed.

Which project factors determine whether a smoke classification is required?

Several project-specific factors determine whether a door at a particular opening must carry a smoke-control classification. The most important is the building’s fire safety design, specifically, whether the compartment boundary at that opening is required to control smoke in addition to limiting fire spread. No single rule applies universally across all building types or applications.

The relevant factors typically include:

  • The function of the compartment boundary. Doors on escape routes, in protected stairwells, or adjacent to refuge areas are more likely to require smoke control than doors between two production areas of equal risk.
  • Applicable regulations and their interpretation. The Dutch BBL establishes minimum building requirements, but the specific classification required for a given opening depends on the project’s fire safety calculation, not on a blanket rule tied to building type. Requirements may be heavier where sector regulations such as PGS15 apply, or where an insurer or client specifies above-statutory performance.
  • The fire safety engineer’s compartmentalisation strategy. The engineer responsible for the fire safety design determines which openings must control smoke, what leakage rate is acceptable, and whether Sa, Sm, or both are needed at each location.
  • The use and occupancy of the building. Facilities with high occupant loads, complex escape routes, or vulnerable occupants may face more demanding smoke-control requirements than single-occupancy industrial buildings with straightforward egress.

Because these factors interact and vary by project, it is not possible to state with certainty that a particular building type always requires (or never requires) a smoke-control classification on its fire doors. The correct approach is to work with a qualified fire safety engineer who can assess the specific building and its fire safety design. Contact Metacon-Next directly if you need guidance on which products carry smoke-control classifications and what documentation supports them.

Need advice for your project?

Discuss your requirements for fire-rated doors, burglar-resistant roller shutters or a suitable solution with Metacon-Next.

Contact us

What documentation confirms a fire door’s smoke-control classification?

A fire door’s smoke-control classification is confirmed by two documents: the classification report issued by the accredited testing laboratory, and the declaration of performance (DoP) issued by the manufacturer under the EU Construction Products Regulation. The CE certificate references the DoP and confirms that the product has been assessed against the applicable harmonised standard; for fire and smoke doors, this is EN 16034 in combination with EN 13241 for industrial doors.

The classification report is the primary technical document. It records the results of the EN 1634-3 smoke control test, the conditions under which the test was conducted, and the classification derived from those results. It also specifies the dimensions and configurations to which the classification applies, and the extended application limits under EN 15269 that define how far the result can be used for untested configurations.

The declaration of performance is the manufacturer’s formal statement of the product’s declared performance characteristics. If a smoke-control classification appears in the DoP, it has been tested and classified. If it does not appear, the product does not carry that classification, regardless of what a product description or sales document might imply.

Architects specifying fire-rated openings should request the classification report alongside the CE documentation at the specification stage. A manufacturer who cannot provide the classification report before commitment to a product leaves a gap in the specification file that can create problems at permit stage or during a building inspection. Metacon-Next’s fire-rated industrial door range is supported by Efectis classification reports available before the order is placed, so specifiers can close their documentation file with confidence.

For any opening where a smoke-control classification is part of the specification, the classification report must confirm that the tested configuration (including door dimensions, frame type, seals, and hardware) falls within the scope of the classification. If the specified opening exceeds the tested or extended application range, a separately tested or assessed solution is required. Requesting a quotation from Metacon-Next at an early stage allows the in-house R&D team to confirm whether a custom configuration can be supported within an existing classification or whether additional assessment is needed.

Passive fire protection documentation (including fire-resistance and smoke-control classification reports, declarations of performance, and Environmental Product Declarations) forms a core part of the specification file for any project where these criteria apply. Metacon-Next publishes its qualification documents openly, reflecting the company’s position that transparency about product performance is a professional obligation, not an optional extra. For architects and specifiers who need to justify their material choices to building inspectors, permit authorities, and clients, that documentation availability is a practical requirement, and one that should be confirmed before a product is written into a specification.