Certification
- tested in accordance with EN 1634-1
- classified according to EN 13501-2
- curtain classified according to EN 13501-1 on fire class B-s1, d0
- validated cycle test in accordance with C2 (> 10.000 cycles)
- CE marked in accordance with EN 13241 and EN 16034
Application
- only suitable for indoor / indoor situations
- only to be used in case of calamity (‘waiting’ function)
- mounting only possible on the wall / opening
- permissible mounting surfaces include: aerated concrete, sand-lime brick, concrete, masonry, fire-resistant steel construction, metal stud wall
Standard
- gravity failsafe tubular motor 230 V incl. control box
- external safety catch device
- optical / acoustic signaling
- galvanized steel side guides and cover box
Options include
- emergency battery (UPS) for maintaining open position in the event of a power failure
- galvanized steel parts powder coated in RAL color of choice
- smoke detector for a stand-alone system
- various switches
- application in situations up to -25 degrees Celsius (freezing/freezing)
classification | fire resistance | max. opening width | max. opening height | max. opening |
---|---|---|---|---|
EW | 60 minutes | 10.000 mm | 8.000 mm | 80 m² |
Due to continuous product development, we ask you to contact us for the current dimensions. Larger dimensions on request.
Downloads
Classification reports
User manuals
Drawings (DWG)
Product specification
Certification
- tested in accordance with EN 1634-1
- classified according to EN 13501-2
- validated cycle test in accordance with C2 (> 10.000 cycles)
- CE marked in accordance with EN 13241 and EN 16034
Application
- only suitable for indoor / indoor situations
- only to be used in case of calamity (‘waiting’ function)
- mounting only possible on the wall / opening
- permissible mounting surfaces include: aerated concrete, sand-lime brick, concrete, masonry, fire-resistant steel construction, metal stud wall
Standard
- gravity failsafe tubular motor 230 V incl. control box
- optical / acoustic signaling
- galvanized steel side guides and cover box
Options include
- emergency battery (UPS) for maintaining open position in the event of a power failure
- galvanized steel parts powder coated in RAL color of choice
- visible parts side guides and cover box in stainless steel 304
- chamfered construction on top of cover box
- smoke detector for a stand-alone system
- various switches
classification | fire resistance | max. opening width | max. opening height | max. opening |
---|---|---|---|---|
EW | 60 minutes | 8.000 mm | 8.000 mm | 48 m² |
EW | 90 minutes | 6.000 mm | 6.00 mm | 19,25 m² |
Due to continuous product development, we ask you to contact us for the current dimensions. Larger dimensions on request.
Downloads
CE Certificate
Classification report
User manuals
Drawings (DWG)
Product specification
Certification
- tested in accordance with EN 1634-1 and EN 1634-3
- classified according to EN 13501-2
- validated cycle test in accordance with C2 (> 10.000 cycles)
- CE marked in accordance with EN 13241 and EN 16034
Application
- only suitable for indoor / indoor situations
- only to be used in case of calamity (‘waiting’ function)
- mounting possible on and in the wall / opening
- permissible mounting surfaces include: aerated concrete, sand-lime brick, concrete, masonry
Standard
- gravity failsafe tubular motor 230 V incl. control box
- optical / acoustic signaling
- galvanized steel side guides and cover box
Options include
- smoke-resistant version based on Sa or S200
- emergency battery (UPS) for maintaining open position in the event of a power failure
- galvanized steel parts powder coated in RAL color of choice
- smoke detector for a stand-alone system
- various switches
classification | fire resistance | max. width | max. height | max. opening |
---|---|---|---|---|
EI(1) | 45 minutes | 7.000 mm | 7.000 mm | ± 35 m² |
EI(2) | 60 minutes | 7.000 mm | 7.000 mm | ± 35 m² |
EW | 120 minutes | 7.000 mm | 7.000 mm | ± 35 m² |
EI(1) | 60 minutes | 7.000 mm | 7.000 mm | ± 24,5 m² |
EI(2) | 120 minutes | 7.000 mm | 7.000 mm | ± 24,5 m² |
EW | 120 minutes | 7.000 mm | 7.000 mm | ± 24,5 m² |
Due to continuous product development, we ask you to contact us for the current dimensions. Larger dimensions on request.
Downloads
Certificates
- CE certificate RGT EI(1) 45 – EI(2) 60 – EW 120 (2434-CPR-0160)
- CE certificate RGT EI(1) 60 – EI(2) 120 – EW 120 (2434-CPR-0159)
- Classification report RGT EI(1) 45 – EI(2) 60 – EW 120 – LBO-0282-KZ
User manuals
Drawings (DWG)
Product specification